THE 4-20mA
CURRENT LOOP
The 4-2OmA
current loop has been with us for so long that it's become rather
taken for granted in the industrial and process sectors alike.
Its popularity comes from its ease of use and its performance.
However, just because something is that ubiquitous doesn't mean
we're all necessarily getting the best out of our current loops.
A big benefit
of the current loop is its simple wiring just the two wires.
The supply voltage and measuring current are supplied over the
same two wires. Zero offset of the base current (ie. 4mA) makes
cable break detection simple: if the current suddenly drops to
zero, you have a cable break. In addition, the current signal
is immune to any stray electrical
interference, and a current signal can be transmitted over long
distances.

Typical
wiring for current output transducer.
You can think
of the current loop itself as being analogous to a water system.
You have a hose pipe (the wires) and a source tap (the power
supply). You have a spray gun that regulates the flow (the transducer).
You can have other equipment on the line, but it all has to be
connected
together in a ring Ioop. The more holes (devices) you have on
the hose pipe, the higher the pressure will be required from
the tap. Relating all that back to the current loop, you see
a power supply, a transducer and one or more pieces of instrumentation
all connected together in a ring.
You'll often
hear things referred to as being either active or passive. Some
instruments have an active output which includes both the control
of the current in the loop as well as provide the supply voltage.
This is typically specified as being a 4-20mA output into 10-750
Ohms, or something similar. A passive input would be a simple
resistor input that
has a voltage drop to be factored into the equation once the
supply voltage is chosen. This is typically specified as a 4-20mA
input into 10 Ohm.
Working out
the power supply requirement is a simple matter of adding up
all the units in the loop at maximum current of 20mA. As an example,
suppose you have a sensor 'regulator' which requires minimum
12V DC and instrumentation of 10 Ohm input:
10 Ohm x 20mA
= 0.2V
So, for this
circuit, a 12.2V minimum supply is required, the sensor's maximum
voltage might be specified at 30V, so a 24V supply would be all
the circuit requirements with spare capacity to boot.
In order to
measure the current loop it is necessary to break the loop and
insert a current meter into it. You can also measure the voltage
across the various components by in the loop, such as the voltage
out of the power supply, the voltage over a sensor, and the voltages
over the various pieces of instrumentation. This information
will give you a
good picture of what is happening within the loop.

Multi-instrument
4-20mA current loop with panel meter, chart recorder, computers,
etc.
A question
which is sometimes asked is whether it is possible to use single
power supply over several loops. This is possible, but you have
to ensure that the power supply can give enough current to meet
the needs of multiple loops. It is also the case that the current
loops will have the same zero negative reference, which can cause
a ground loop. In addition, interference from one loop can affect
all the other loops driven from the one supply.
This article
is printed with the kind permission of Morten Moller